November 20, 2026A two-wire 4–20 mA pressure transmitter is wired in series with its DC supply and the control-system input: the positive supply feeds the transmitter, and the transmitter return goes to the analogue input return or 0 V, according to the system drawing. Before energising, confirm the transmitter range, supply voltage, terminal identification, polarity and total loop load. Then measure loop current by opening the circuit and inserting the meter in series—not across the supply.
What a two-wire 4–20 mA loop contains
In a standard two-wire installation, the same pair of conductors carries both DC power and the measurement signal. The transmitter regulates the loop current between 4 mA and 20 mA in proportion to the measured pressure. The receiving device—PLC, engine monitoring system, alarm module or display—detects that current and scales it to pressure.
A typical loop arrangement is:
- DC supply positive to the transmitter positive or loop-positive terminal.
- Transmitter negative or loop-return terminal to the analogue input positive terminal.
- Analogue input return or 0 V back to DC supply negative.
Do not assume terminal names or connector pin numbers. Use the transmitter marking, supplied connector diagram and OEM or installation documentation. Some transmitters use a DIN-style connector or a detachable terminal insert, and the physical position of the pins is not enough to identify polarity.
Safety and preparation
- Apply electrical isolation and lock-out/tag-out before opening a panel, junction box or transmitter connector.
- Stop or secure the associated machinery where access to the pressure connection could create a hazard.
- Isolate and depressurise the pressure line before removing a transmitter. Confirm zero pressure with an appropriate gauge or approved procedure.
- Check whether the loop is powered by the control system, a local instrument supply or an intrinsic-safety interface. Do not connect a second supply unless the wiring diagram permits it.
- Use a calibrated multimeter with suitable CAT and voltage ratings, and follow the transmitter and machinery OEM manuals.
Record the existing wire colours, terminal numbers, connector orientation and cable screen arrangement before disconnection. Wire colour is an identification aid only; it is not a substitute for a circuit diagram.
Step-by-step wiring procedure
1. Confirm the transmitter and application
Read the nameplate and compare it with the job documentation. Verify:
- Pressure range and whether it is gauge, absolute or differential pressure.
- Output type: two-wire, 4–20 mA.
- Permitted DC supply range.
- Connector type, terminal designations and environmental protection.
- Process connection and mechanical fit, using the equipment drawing or OEM parts list.
For example, the Trafag Picotrans 8244.78.2318 Pressure Transmitter is specified as 0–10 bar gauge, 4–20 mA and 10–34 V DC, while the Trafag Picotrans NP 8244.81.2318 Pressure Transmitter is specified as 0–40 bar gauge, 4–20 mA and 10–34 V DC. These ranges are not interchangeable merely because both devices use the same signal.
2. Identify loop-positive and loop-return terminals
Locate the transmitter’s positive and negative loop terminals from the product marking or wiring diagram. On an existing installation, trace the conductors back to the junction box or input card rather than relying only on colour.
Identify the analogue input terminals separately. A channel may be configured for loop-powered current input, externally powered current input or another signal type. A two-wire transmitter must be connected to a compatible current-input circuit. Never connect it directly to a voltage-only input without the specified signal-conditioning hardware.
3. Check supply voltage and loop-load capacity
Confirm that the available DC supply remains within the transmitter’s specified range at the transmitter terminals, including voltage drop in the cable and input device. The basic compliance check is:
Available voltage for load = supply voltage − minimum transmitter operating voltage
The available voltage for the input load and cable must be at least the voltage required at the maximum loop current:
Required load voltage = 0.020 A × total loop resistance
For example, a 250 Ω input requires 0.020 × 250 = 5 V at 20 mA. The calculation must also include cable resistance and any isolator, barrier or indicator in the loop. If the supply cannot maintain the transmitter’s required voltage at 20 mA, the signal may fail to reach full scale or become unstable.
4. Make the connections with power isolated
- Confirm the supply is isolated and prove dead with the approved test method.
- Terminate the supply positive conductor on the transmitter loop-positive terminal.
- Terminate the transmitter loop-return conductor on the analogue input positive or current-input terminal.
- Connect the analogue input return to the DC supply negative or designated loop return, as shown on the system drawing.
- Tighten and secure terminals according to the connector or panel manufacturer’s instructions. Do not invent a torque value if it is not specified.
- Refit connector seals, glands and covers so the installed protection level is maintained.
For a replacement supplied with a connector plug, inspect the plug insert and sealing parts before use. A correct transmitter can still produce an intermittent signal if the connector pins are loose, contaminated or incorrectly assembled.
5. Check polarity before energising
With the circuit still isolated, perform a continuity and polarity review against the wiring diagram. Check that:
- The transmitter is not shorted directly across the DC supply.
- The analogue input is in the current path, not bypassed.
- Positive and return conductors have not been reversed.
- The cable screen is not being used as a current-carrying conductor.
- No shield or drain wire is accidentally touching a signal terminal.
If the circuit includes a fuse, isolator or barrier, verify its rating and position. Never use a resistance test on a live circuit, and disconnect sensitive input electronics before applying any test voltage not explicitly permitted by the OEM.

Commissioning and measuring the 4–20 mA signal
After the wiring review is complete, restore power in accordance with the machinery isolation procedure. Allow the control system and transmitter to initialise, then confirm the loop current at a known pressure condition.
Measure current in series
- Set the multimeter to the appropriate DC current range and verify the lead positions. Check the meter fuse and rating.
- Isolate the loop before opening it, where required by the site procedure.
- Open one loop conductor at an accessible test point.
- Connect the meter leads between the two separated points so the complete loop current passes through the meter.
- Restore power and read the current.
- Isolate the circuit before removing the meter and restoring the permanent connection.
A meter connected across the supply or input terminals in current mode can create a short circuit, blow the meter fuse or damage the loop. If the installation has a designated current test socket, use it according to the panel documentation.
Use the correct scaling calculation
For a linear transmitter, calculate expected current using:
I = 4 mA + 16 mA × [(P − Pmin) ÷ (Pmax − Pmin)]
For a 0–10 bar transmitter at 6 bar:
I = 4 + 16 × (6 ÷ 10) = 13.6 mA
For a 0–8 bar transmitter at 4 bar:
I = 4 + 16 × (4 ÷ 8) = 12 mA
At the lower range value the expected signal is 4 mA; at the upper range value it is 20 mA. A current below or above these values may indicate an actual process condition, wiring fault, insufficient loop voltage or transmitter fault. The related article on 4–20 mA troubleshooting covers fault interpretation; this procedure focuses on correct wiring and commissioning.
Shielding, routing and noise control
Route analogue signal cable away from high-current motor cables, alternator leads, ignition wiring, solenoid wiring and variable-frequency drive output cables. Cross power cables at approximately 90 degrees where separation is not possible. Avoid unnecessary cable loops and protect the cable from vibration, heat, oil and chafe.
- Use the cable type specified by the installation or OEM documentation.
- Terminate the screen or drain wire exactly as the control-system design requires; commonly, a screen is bonded at one designated end to avoid circulating currents, but the system drawing takes precedence.
- Do not connect the screen at both ends merely as a general rule.
- Keep transmitter signal conductors separated from noisy switching circuits inside junction boxes and panels.
- Ensure glands and connector backshells provide strain relief without crushing the cable.
Final field checklist
| Check | Acceptable result |
|---|---|
| Transmitter range | Matches the machinery documentation and control-system scaling. |
| Output | Two-wire 4–20 mA is confirmed. |
| Supply | Within the transmitter rating at the transmitter terminals. |
| Polarity | Positive, return and input terminals match the wiring diagram. |
| Loop load | Supply has adequate voltage at 20 mA after all resistance is included. |
| Signal | Measured in series and consistent with applied pressure. |
| Cable | Shielding, routing, glands and strain relief are correct. |
| Process connection | Leak-free and installed only after isolation and depressurisation. |
When selecting a replacement, verify the complete part number, range, output, supply, connector and process connection against the engine or compressor documentation. The MTU 005 535 10 31 Pressure Transmitter is specified as type 8212.26.2210, 0–8 bar gauge, 4–20 mA and 12–36 V DC. Its stated equivalence to the supplied Trafag type should not be extended to other ranges or connectors without OEM documentation. Genuine parts supplied in original packaging should still be checked against the equipment parts list before installation.
FAQ
Can a two-wire transmitter be wired directly to a 24 V DC supply?
Only if the transmitter’s specified supply range and the complete loop design permit it. Confirm the input load and cable resistance before energising.
Where should the ammeter be connected?
In series with one loop conductor. Never connect a current meter directly across the DC supply or transmitter terminals.
What does 4 mA represent?
For a normally scaled linear transmitter, 4 mA represents the lower configured range value, while 20 mA represents the upper value. Confirm whether the transmitter is gauge, absolute or otherwise configured.
Can two 4–20 mA transmitters with the same output be interchanged?
No. Range, supply, connector, process connection, mechanical fit and OEM part-number compatibility must all be verified.