November 20, 2026For a linear 4–20 mA pressure sensor, 4 mA represents the lower range value and 20 mA represents the upper range value. For the catalogue ranges covered here, that means 0 bar at 4 mA and respectively 8, 16 or 30 bar at 20 mA. The pressure calculated from a measured loop current is:
Pressure = (measured current − 4 mA) ÷ 16 mA × sensor span
Thus, 12 mA is the midpoint: 4 bar on a 0–8 bar transmitter, 8 bar on a 0–16 bar transmitter and 15 bar on a 0–30 bar transmitter. Confirm the sensor range and whether it measures gauge or absolute pressure before entering any PLC scale.
Understand the 4 mA and 20 mA endpoints
A conventional two-wire transmitter is powered by the same loop that carries its signal. The transmitter regulates loop current between 4 and 20 mA in proportion to pressure. The receiving input, such as a PLC analogue card or engine-monitoring module, measures that current and converts it into an engineering value.
The nominal endpoint relationship is:
| Loop current | Signal position | 0–8 bar sensor | 0–16 bar sensor | 0–30 bar sensor |
|---|---|---|---|---|
| 4 mA | 0% | 0 bar | 0 bar | 0 bar |
| 8 mA | 25% | 2 bar | 4 bar | 7.5 bar |
| 12 mA | 50% | 4 bar | 8 bar | 15 bar |
| 16 mA | 75% | 6 bar | 12 bar | 22.5 bar |
| 20 mA | 100% | 8 bar | 16 bar | 30 bar |
These values assume a linear transmitter and a correctly configured input. A current slightly below 4 mA or above 20 mA may indicate a fault, diagnostic condition, wiring problem or an out-of-range process condition; interpret it according to the transmitter and monitoring-system documentation.
Calculate pressure from loop current
Use the transmitter’s span, not the maximum pressure it can withstand. For example, the MTU 005 535 10 31 Pressure Transmitter has a 0–8 bar gauge range and a stated maximum pressure of 16 bar. Its scaling span is 8 bar, not 16 bar.
Example: 0–8 bar range
If the loop current is 14 mA:
Pressure = (14 − 4) ÷ 16 × 8 = 10 ÷ 16 × 8 = 5 bar
At 5 mA, the result is 0.5 bar. At 19 mA, it is 7.5 bar. Do not round the current prematurely when using a high-resolution input; retain sufficient decimal places for the required display accuracy.
Example: 0–16 bar range
For a 0–16 bar transmitter at 15 mA:
Pressure = (15 − 4) ÷ 16 × 16 = 11 bar
The MTU 001 535 90 31 Pressure Transmitter is specified as 0–16 bar gauge with a 4–20 mA output. If the input is correctly scaled, 15 mA should therefore display approximately 11 bar, subject to transmitter, wiring and input accuracy.
Example: 0–30 bar range
For a 0–30 bar transmitter at 10 mA:
Pressure = (10 − 4) ÷ 16 × 30 = 11.25 bar
The MTU 005 535 13 31 Pressure Sensor is specified as 0–30 bar relative pressure. At 10 mA, its calculated pressure is 11.25 bar, not 15 bar; 15 bar occurs at the midpoint current of 12 mA.
Configure the PLC or engine-monitoring input
Most analogue input modules provide either direct low/high scaling or a raw-count calculation. The essential entries are the signal type, lower and upper current limits, and lower and upper engineering values.
- Confirm that the channel is configured for a current input, normally 4–20 mA, rather than a voltage input.
- Enter the lower signal value as 4 mA and the upper signal value as 20 mA. Some systems use raw counts instead, so use the input card’s documented counts for these endpoints.
- Enter the engineering range from the transmitter data: 0 and 8 bar, 0 and 16 bar, or 0 and 30 bar.
- Set the displayed unit deliberately. If the process documentation uses bar, keep the alarm, trend and display values in bar unless a controlled conversion to another unit is required.
- Configure under-range and over-range diagnostics separately from the process alarm. A low-current diagnostic threshold is not the same as a low-pressure alarm.
- Record the configured range, channel number, sensor part number and test current in the commissioning record.
For a raw analogue value, the equivalent calculation is:
Engineering value = (raw value − raw-at-4-mA) ÷ (raw-at-20-mA − raw-at-4-mA) × span
Use the raw-count limits published for the particular input module. Do not assume that every PLC uses the same count range or that 4 mA equals zero counts.
Safety note: Isolate and lock out the relevant electrical supply before changing wiring or terminals. If the pressure connection must be disturbed, isolate the process, depressurise and drain it safely before removing the transmitter. Follow the OEM manual, vessel procedures and the input-module documentation.

Commissioning checks at the sensor and input
A correct software formula cannot compensate for a wrong sensor range, poor termination or trapped process pressure. Perform the following checks in a controlled condition.
- Verify identification. Compare the installed part number, pressure range, output and supply requirement with the engine parts list and the transmitter documentation. Do not substitute a 0–30 bar device for a 0–8 bar device merely because both provide 4–20 mA.
- Check the loop supply. The 0–8 bar and 0–30 bar devices listed here specify 12–36 V DC; the 0–16 bar device specifies 12–34 V DC. Verify the available voltage at the transmitter terminals under load, not only at the power supply.
- Inspect polarity and terminations. Check the two-wire loop polarity, terminal tightness, cable condition, shield arrangement and any junction boxes. Follow the equipment wiring drawing rather than relying on connector appearance.
- Establish a safe reference pressure. At a known zero or reference condition, allow the process to stabilise. A gauge transmitter should be referenced to atmospheric pressure when correctly isolated and vented, where the installation permits this safely.
- Measure loop current. Use a calibrated current measurement method suitable for the circuit. Opening a live loop to insert a meter can interrupt power to the transmitter, so use the approved test terminals or loop calibrator arrangement.
- Compare the display. Calculate the expected pressure from the measured current and compare it with the PLC or monitoring display. Investigate any difference before changing the scaling.
- Test alarms carefully. Where permitted by the maintenance procedure, use a simulator or controlled process condition to verify alarm thresholds, delay timers, shutdown logic and the displayed unit. Do not create an unsafe engine condition merely to prove an alarm.
Identify zero and span errors
A zero error shifts the complete measurement up or down. For example, if a known zero-pressure condition produces 5 mA on a nominal 0–8 bar sensor, the indicated pressure from the ideal formula is 0.5 bar. First check trapped pressure, isolation valves, impulse-line blockage, wiring and instrument condition; do not immediately alter the PLC zero.
A span error changes the slope. If the signal is correct or nearly correct at zero but does not reach the expected value at a known reference pressure, check the transmitter range, calibration, supply voltage and input configuration. A 0–30 bar sensor fitted where an 0–8 bar sensor is expected will appear to have a major span error even though the transmitter may be operating normally.
| Symptom | Likely cause | First checks |
|---|---|---|
| Display is exactly half the expected pressure | Wrong range entered, such as 0–16 instead of 0–8 bar | Compare transmitter nameplate or part number with PLC span |
| Display remains near zero with a healthy loop | Input scaled for the wrong signal or range | Check 4–20 mA channel type and engineering limits |
| Display is offset at zero pressure | Trapped pressure, zero shift or wiring/input error | Isolate and vent safely; verify current independently |
| Reading is unstable | Electrical interference, loose termination or fluctuating process | Inspect terminals, shielding, supply and process pulsation |
| Current is below 4 mA or above 20 mA | Fault, diagnostic state, supply problem or over-range condition | Check transmitter documentation, loop voltage and process condition |
Do not mix gauge and absolute pressure
Gauge, relative and absolute pressure are not interchangeable. Gauge pressure is referenced to local atmospheric pressure; absolute pressure is referenced to a vacuum. A 0–8 bar gauge transmitter reads approximately zero when exposed to atmosphere, while an absolute transmitter at atmosphere reads approximately atmospheric pressure in the selected pressure unit.
The listed 0–8 and 0–16 bar devices are specified as gauge ranges, and the 0–30 bar device is specified as relative pressure. Configure and document them accordingly. If the engine manual, alarm list or control system calls for absolute pressure, confirm that the installed transmitter is the correct absolute-pressure type; do not convert a gauge signal by simply changing the PLC label.
Replacement and interchangeability checks
A matching 4–20 mA output alone does not prove interchangeability. Before replacement, verify all of the following against the OEM parts list and installation drawing:
- OEM part number or documented supersession.
- Pressure reference: gauge, relative or absolute.
- Pressure range and overload requirement.
- Two-wire output and supply-voltage requirement.
- Mechanical connection, sealing arrangement, connector and orientation.
- Environmental and approval requirements for the installation.
The product data identifies the 0–8, 0–16 and 0–30 bar transmitters by specific MTU and Trafag type references, but it does not establish universal interchangeability between them. Verify the part number against the engine’s parts list before ordering or installing.
Commissioning checklist
- Range: the configured span matches the installed transmitter.
- Endpoints: 4 mA is configured as the lower value and 20 mA as the upper value.
- Reference: gauge/relative versus absolute pressure is confirmed.
- Supply: DC voltage is within the specified transmitter range under load.
- Current: measured loop current agrees with the calculated pressure.
- Alarms: process alarms and instrument diagnostics are tested separately.
- Records: channel, part number, range, test readings and date are documented.
FAQ
What pressure does 12 mA represent?
It represents 50% of span: 4 bar on 0–8 bar, 8 bar on 0–16 bar and 15 bar on 0–30 bar.
Can I scale a 0–30 bar sensor as 0–8 bar?
No. The PLC scale must match the installed transmitter range unless the OEM control design explicitly specifies another signal conversion.
Does maximum pressure determine the PLC span?
No. Use the calibrated measurement range. Maximum or overload pressure is a withstand rating, not the 20 mA endpoint.
Why is gauge pressure important?
Gauge or relative pressure is referenced to atmosphere, while absolute pressure is referenced to a vacuum. Mixing them can create a constant measurement error and incorrect alarms.