MTU 0055351031 vs 0055351331: Key Differences
November 20, 2026
How to Choose the Correct MTU Pressure Transmitter
November 20, 2026Pressure transmitter range selection for engine alarms is a balance between protection and measurement quality. Select the narrowest pressure range that safely covers the normal operating pressure, the alarm and shutdown thresholds, and credible pressure transients. A range that is unnecessarily wide will produce fewer milliamps per bar and less usable signal resolution near the alarm point; a range that is too narrow may saturate during a spike or fail prematurely.
The transmitter is only one part of the measurement chain. The engine controller, alarm setpoint, input scaling, wiring, process connection and replacement part number must all agree. The procedure below is intended for marine diesel engines and gensets, but the final selection remains subject to the engine maker’s parts list and maintenance documentation.
1. Start with the actual pressure operating window
Record the pressure expected at the measuring point, not a value taken from a different circuit. Oil pressure, fuel pressure, cooling-water pressure, charge-air pressure and hydraulic pressure can require very different ranges even on the same engine.
- Identify the exact measuring point and whether the specified pressure is gauge or absolute. The products discussed here are gauge transmitters.
- Record the normal pressure at cold start, warm idle, rated load and any other relevant operating condition.
- Record the alarm, warning and shutdown thresholds from the controller configuration or OEM documentation.
- Find the highest credible pressure, including pump dead-head conditions, valve closure, start-up transients and pulsation. Use the OEM manual, system design data and maintenance history.
- Confirm whether the transmitter sees pressure directly or through a restriction, snubber, impulse line or remote connection. These items can affect transient exposure and response.
Do not select a range solely because its maximum value is above the normal running pressure. The alarm point must sit far enough above the lower end to be represented accurately, while the maximum pressure rating must not be exceeded during installation or operation.
2. Match range to alarm accuracy and signal resolution
A standard two-wire 4–20 mA transmitter represents the selected pressure span with 16 mA. For a transmitter with lower range value PL and upper range value PU:
Output current = 4 mA + 16 mA × (pressure − PL) ÷ (PU − PL)
For a 0 bar lower range, the signal change per bar is 16 divided by the full-scale range. Therefore, a 0–4 bar transmitter produces 4 mA per bar, a 0–8 bar transmitter produces 2 mA per bar, and a 0–50 bar transmitter produces 0.32 mA per bar.
| Transmitter range | Current change per bar | Signal at 2 bar | Practical implication |
|---|---|---|---|
| 0–4 bar | 4.00 mA/bar | 12.00 mA | High signal change per bar, but limited pressure headroom |
| 0–8 bar | 2.00 mA/bar | 8.00 mA | More headroom with lower signal change per bar |
| 0–50 bar | 0.32 mA/bar | 4.64 mA | Suitable only where the process pressure requires this span |
The table demonstrates why a 0–50 bar transmitter is not an acceptable substitute for a low-pressure alarm merely because both devices output 4–20 mA. If the controller is scaled for 0–4 bar, a 0–50 bar transmitter will be interpreted incorrectly. Even if the controller is re-scaled, a given current change represents much more pressure on the wider-range device.
Resolution is determined by both transmitter span and the receiving input. For example, if an analogue input digitises 16 mA over 4,096 counts, a 0–4 bar transmitter gives approximately 1,024 counts per bar, while a 0–50 bar transmitter gives approximately 81.9 counts per bar. Actual alarm accuracy also depends on transmitter accuracy, input accuracy, electrical noise, pressure pulsation and the controller’s alarm filtering. Do not claim a final alarm tolerance unless those specifications are available.
3. Check transients, overload and mechanical protection
Pressure spikes must be considered separately from the normal measurement range. A transmitter’s stated maximum or overload pressure is not automatically a continuous operating pressure, and it does not replace system protection. Confirm the permitted conditions in the specific datasheet and OEM manual.
- Check startup: determine whether a pump or regulator can briefly exceed the normal pressure before control stabilises.
- Check valve action: rapid valve closure can create a pressure surge that is not visible on a slowly updated display.
- Check pulsation: reciprocating pumps and engine-driven circuits may impose repeated peaks on the sensing element.
- Check isolation: use a suitable isolating valve and, where specified by the system designer, a snubber or pulsation damper.
- Check installation: protect the connector and cable from heat, vibration, oil, water ingress and mechanical strain.
For example, the MTU 001 535 86 31 Pressure Transmitter (Trafag 8842.76.2210, 0–4 bar, 4–20 mA) has a stated 0–4 bar gauge range and 8 bar maximum pressure. The MTU 005 535 10 31 Pressure Transmitter (Type 8212.26.2210, 0–8 bar, 4–20 mA) has a 0–8 bar gauge range and 16 bar maximum pressure. These figures help compare the supplied parts, but they do not establish that either device is suitable for a particular engine position without checking the engine documentation.

4. Verify controller scaling before fitting the spare
A two-wire transmitter uses the same pair of conductors for power and signal. The loop supply must provide the transmitter’s specified voltage and enough compliance voltage for the transmitter, input resistance and cable losses. Never assume that a 24 V nominal supply is suitable without checking the transmitter data and the actual loop.
- Confirm the transmitter output is 4–20 mA and two-wire, rather than a voltage output or a three-wire device.
- Confirm the supply range. For example, the 0–4 bar MTU 001 535 86 31 is specified for 12–34 V DC; the 0–8 bar MTU 005 535 10 31 and 0–50 bar MTU 005 535 15 31 are specified for 12–36 V DC.
- Check the controller’s configured lower and upper pressure values. For a 0–8 bar transmitter, 4 mA should correspond to 0 bar and 20 mA to 8 bar unless the OEM configuration states otherwise.
- Check the alarm setpoint in engineering units, not only as a raw current value. A low-pressure alarm at 2 bar on a 0–8 bar range corresponds to 8 mA using the formula above.
- Compare the controller display with an independent calibrated pressure indication where practical. Do not use an unverified display as the reference for calibration.
If a replacement has a different range, output type, supply requirement or connector arrangement, treat it as a different device. Do not correct a mismatch by changing controller scaling unless the OEM documentation authorises that configuration and the alarm logic has been fully verified.
5. Selection and replacement checklist
Use this checklist before releasing a pressure transmitter spare for installation:
- Engine model, serial number and exact measuring point recorded.
- Gauge or absolute pressure confirmed.
- Normal pressure, alarm pressure and maximum credible transient documented.
- Range selected with sufficient measurement resolution at the alarm point.
- Maximum pressure or overload capability checked against the application.
- 4–20 mA loop type, supply voltage and controller input confirmed.
- Process connection, electrical connector and physical fit checked against the OEM parts information.
- Part number and any documented supersession verified through OEM records.
- Controller scaling, alarm delay and shutdown logic recorded before removal.
Before removal, stop the relevant equipment and apply the vessel or site isolation and lock-out procedure. Isolate the pressure source, depressurise the sensing line and verify zero pressure before loosening the transmitter. Electrical isolation is also required where the loop or adjacent equipment presents a shock or short-circuit hazard. Follow the OEM manual and the vessel’s permit-to-work requirements.
After installation, inspect for leakage, confirm correct cable termination and energise the loop only after the process connection is secure. Check the live current at a known pressure, compare the controller display with the expected scaled value and test the alarm using the approved commissioning method. Do not create a hazardous pressure condition simply to prove an alarm.
6. Document the selected spare
Record the selected transmitter as an engine-specific spare, not merely as a generic “4–20 mA pressure sensor”. Include the engine and measuring point, range, gauge or absolute reference, output, supply voltage, connector and process connection, controller scaling, alarm setpoint, part number and verification source.
For example, the MTU 005 535 15 31 Pressure Transmitter 8212 Minitrag (0–50 bar, 4–20 mA) is specified as a 0–50 bar gauge transmitter with a 100 bar maximum pressure and 12–36 V DC supply. Its wide span makes it unsuitable for a low-pressure alarm unless the pressure point and controller configuration genuinely require that range. The supplied product data identifies it as new old stock in original packaging; storage condition and date code should still be recorded in the spare-parts system.
Keep one approved record with the engine documentation and one with the stores or planned-maintenance system. When ordering a replacement, verify the exact OEM part number rather than relying on appearance or a similar Trafag type designation. Cross-interchangeability should be accepted only when supported by OEM documentation or a documented supersession.
FAQ
Should I choose the smallest possible pressure range?
Choose the narrowest range that safely covers normal pressure, alarm thresholds and credible transients. A range that is too narrow can saturate or be damaged; a range that is unnecessarily wide reduces signal change per bar.
Can any 4–20 mA transmitter replace another?
No. Range, gauge or absolute reference, supply voltage, connector, process connection, physical fit and controller scaling must all match. Verify the OEM part number or documented supersession.
How do I calculate current at the alarm pressure?
Use 4 mA + 16 mA × (alarm pressure − lower range) ÷ span. For a 0–8 bar transmitter at 2 bar, the expected current is 8 mA.
Does the maximum pressure rating permit continuous operation?
Not necessarily. Treat the stated maximum or overload value as a limit requiring interpretation from the applicable datasheet and OEM manual, not as a continuous operating rating.