November 20, 2026Effective 3/2 way solenoid valve troubleshooting starts by separating the fault into three areas: control signal, pneumatic supply and valve mechanics. Confirm the valve receives the correct command and coil voltage, then prove that air reaches the correct port and that the spool or poppet changes state. Only after these checks should you condemn the coil or complete valve.
Work from the outside in. Record the original tube connections and valve position before disturbing anything, and use the valve markings rather than assuming which port is supply, actuator or exhaust. A 3/2-way valve has three ports and two switching positions; its exact normally closed or normally open function depends on the valve design and installation.
Safety and preparation
- Obtain the approved work permit and follow the vessel, plant and OEM isolation procedure.
- Isolate electrical power, apply lock-out/tag-out and prevent an automatic or remote command from energising the valve.
- Shut off the pneumatic supply and depressurise the valve, tubing and actuator before loosening any connection.
- Be aware that an actuator may move when trapped air is released. Secure connected machinery and confirm the safe state.
- Use a meter rated for the circuit, suitable test leads and correct personal protective equipment.
- Do not remove the coil or valve body from a pressurised system. Follow the OEM manual for installation, cleaning and functional testing.
Useful tools include a calibrated multimeter, test lamp where appropriate, pressure gauge or portable pneumatic test set, insulated probes, small hand tools and approved leak-detection fluid. A wiring diagram and the valve’s installation instructions are more reliable than colour coding or assumptions from a similar machine.
1. Confirm the symptom and installation
First define what “failed” means. Is the actuator not extending, not retracting, moving slowly, moving intermittently, or failing to hold position? Check whether the fault occurs only during a remote command, only when another load starts, or continuously. These observations help distinguish a control problem from a valve or air problem.
| Symptom | Likely causes | First checks |
|---|---|---|
| No movement and no audible valve action | No command, open circuit, incorrect voltage, failed coil or seized valve | Command status, voltage at the coil, coil continuity and manual override |
| Valve clicks but actuator does not move | No supply pressure, wrong port connection, blocked tube, insufficient flow or actuator fault | Pressure at the supply port, port identification, tubing and actuator |
| Actuator moves in the wrong direction | Ports crossed, valve function misunderstood or tubing altered | Compare connections with the schematic and valve markings |
| Slow or incomplete movement | Low pressure, restricted exhaust, contamination, undersized tubing or actuator friction | Pressure while operating, exhaust path, fittings and mechanical load |
| Continuous air leakage | Damaged seal, contaminated seat, loose fitting or incorrect exhaust routing | Leak location, connections, valve body and actuator seals |
2. Check air supply and port connections
- Verify that the upstream isolation valve is open and that the regulator is set within the valve’s permitted operating range. For the IMI Herion 2401135, the stated operating pressure is 0–10 bar; do not exceed the product rating or assume that the connected actuator has the same limit.
- Check pressure at the valve inlet, not only at a distant header. Pressure can collapse through a blocked filter, closed isolation valve, faulty regulator or restricted tube.
- Identify the three ports from the valve marking and schematic. In general, one port is the pressure inlet, one connects to the actuator and one exhausts; the numbering and normal state must be confirmed for the actual valve.
- Inspect tubing for kinks, crushed ends, contamination and incorrect insertion depth. Check fittings for leaks without applying excessive force.
- Operate the valve and observe pressure at the actuator connection. If inlet pressure is present but the output does not change state, continue with the electrical and mechanical checks.
A valve can click normally while delivering no useful airflow if the exhaust silencer is blocked or if the supply and actuator ports have been transposed. Remove and inspect a silencer only after isolation and depressurisation. Do not use compressed air to blow debris towards personnel or sensitive equipment.

3. Confirm the electrical command at the valve
Measure at the coil terminals while the control system is commanding the valve. Measuring at the PLC or relay alone can miss a broken conductor, poor terminal, incorrect common or voltage drop in the field wiring. Compare the measured voltage with the coil marking and control drawing.
- With the command off and the circuit safely isolated, inspect the connector, pins, cable gland, terminals and earth or common connection for moisture, looseness or corrosion.
- Restore power only under the approved test procedure. Command the valve and measure directly across the coil terminals. A nominal 24 V DC coil should receive the specified DC supply at the valve; do not substitute AC or a different voltage.
- If voltage is absent, trace backwards through the fuse, output module, relay, interlock, emergency-stop circuit and cable. Check whether the control system is withholding the command because a permissive is not satisfied.
- If voltage is correct but there is no audible or mechanical response, isolate again and test the coil and valve movement separately.
The IMI Herion 2401135 3/2-Way Solenoid Poppet Valve is supplied with a 24 V DC, 11 W coil and is rated for 100% duty cycle. Its nominal resistance calculated from the nameplate values is approximately 52 ohms using R = V²/P: 24²/11 = 52.36 ohms. This is only a reference calculation. Actual measured cold resistance varies with winding temperature, meter accuracy and manufacturing tolerance, so use the OEM or manufacturer test limits where provided.
4. Test coil continuity and condition
Isolate the supply, disconnect the coil from the circuit and measure resistance across its terminals. An open circuit strongly indicates a broken winding or connection. A very low resistance compared with the expected value suggests a shorted winding, but interpret the result with the manufacturer’s limits and the coil temperature.
- Open circuit: check the connector and terminals once more, then replace the coil if the winding remains open.
- Resistance substantially outside the permitted range: compare with a known-good coil of the same specification before condemning it.
- Correct resistance but no actuation: check that the coil is receiving its rated voltage under load and that the valve armature or poppet is not seized.
- Burning smell, discolouration, cracked encapsulation or water ingress: remove from service and investigate the cause, including overvoltage, incorrect duty, heat and contamination.
Never energise a loose coil beside ferrous tools or allow a coil to remain powered during an unauthorised bench test. The magnetic field and hot surfaces can create additional hazards. Refit the connector seal and strain relief correctly after testing.
5. Use the manual override and check spool movement
After electrical isolation and confirmation that movement is safe, use the manufacturer’s manual override as instructed. It is a diagnostic aid, not a substitute for normal control. If the actuator changes state when the override is operated, the pneumatic circuit and valve mechanism may be functional and the electrical command remains suspect.
If the override is stiff, ineffective or does not produce a pressure change, possible causes include a seized armature, contaminated poppet seat, damaged spring, blocked passage or incorrect porting. Do not force the override or dismantle the valve in service. Remove the valve only after isolation, depressurisation and identification of all tubes.
6. Check leakage and blocked exhaust
With the valve in each commanded state, listen for escaping air and apply approved leak-detection fluid to external joints. Bubbles at a fitting indicate an external connection leak; leakage through the valve’s exhaust can indicate a damaged seat, seal contamination or a valve that is not reaching its end position.
Inspect the exhaust port and silencer for oil, dirt, corrosion or ice where relevant. A restricted exhaust can prevent a spring-return actuator from releasing or can make operation slow. Never plug an exhaust merely to stop noise or leakage: doing so can change the valve function and create trapped pressure.
7. Decide whether to replace the coil or valve body
Replace the coil when the electrical tests identify an open, shorted or thermally damaged winding and the valve changes state correctly with a sound coil or manual override. Replace the valve body when the coil receives the correct voltage and tests correctly, but the poppet or spool remains stuck, internal leakage persists, passages are damaged, or the valve fails its functional test after cleaning permitted by the manufacturer.
Do not select a replacement by appearance alone. Verify all of the following against the engine parts list, pneumatic schematic and OEM documentation:
- Exact part number and any documented supersession.
- 3/2-way function and spring-return or other normal state.
- Operating pressure and temperature range.
- Coil voltage, AC or DC type, power or current and duty rating.
- Port size, thread standard, connector arrangement and mounting dimensions.
- Flow capacity and compatibility with the actuator and air quality requirements.
The IMI Herion 2401135 is a brass-bodied, direct solenoid-actuated poppet valve with spring return and manual override, rated 0–10 bar and −10 to +60 °C, with an IP65 24 V DC coil. These details do not prove interchangeability with another installed valve. Verify the part number against the engine or machine parts list before ordering. It is supplied as unused new old stock in original packaging with installation and operating instructions.
Final functional test
- Confirm all tubes are connected to the correct marked ports and secured.
- Remove tools, temporary jumpers and test instruments from the work area.
- Restore pneumatic pressure gradually and inspect for leaks.
- Restore electrical power under the approved procedure.
- Command the valve several times locally and remotely, checking actuator travel, response time, exhaust and fail-safe position.
- Record measured voltage, coil resistance, supply pressure, defect found, replacement part number and test result.
If the valve passes a bench test but fails in operation, investigate the control interlocks, pressure drop under demand, actuator load and machine sequence rather than replacing the same valve again. If the fault is intermittent, retain the failed coil or valve for inspection and record temperature, vibration and command history.
FAQ
What voltage should I measure at a 24 V DC solenoid coil?
Measure directly across the coil terminals while it is commanded. It should receive the specified 24 V DC nominal supply; confirm the permitted tolerance in the valve or control-system documentation.
Can a solenoid valve click and still be faulty?
Yes. A click proves that the armature may move, but not that the correct ports are connected, the poppet seals, the exhaust is clear or sufficient airflow reaches the actuator.
Should I replace the coil or the complete valve?
Replace the coil when its electrical condition is defective and the valve mechanism operates correctly. Replace the valve body when mechanical movement, sealing or internal passages fail after the coil and installation have been proven.
Is a different 3/2-way valve interchangeable?
Not automatically. Match the function, normal state, pressure, temperature, coil supply, connector, ports, dimensions and documented part-number supersession against the OEM information.