Solenoid Coil Failure: Open Circuit or Overheating
November 20, 2026
How to Diagnose a 3/2-Way Solenoid Valve Fault
November 20, 2026The IMI Herion 2401135 is a directly actuated 3/2-way pneumatic poppet valve with spring return, a 24 V DC, 11 W coil and manual override. To test it correctly, first confirm the identification and application, then isolate the circuit, check the coil electrically, and finally prove the de-energised and energised air paths within the valve’s rated 0–10 bar operating range.
1. Confirm the valve identity and application
Before removing a suspected faulty valve, compare the installed part with the equipment parts list and the valve markings. The relevant identification for this item is IMI Herion Id. Nr. 2401135, also written as 2401135. The product data identifies it as a brass-bodied, 3/2-way, direct solenoid-actuated poppet valve with spring return.
- Valve function: 3/2-way poppet type.
- Actuation: direct solenoid operation.
- Return: mechanical spring return when the coil is de-energised.
- Operating pressure: 0–10 bar.
- Ambient temperature: −10 to +60 °C.
- Coil: 24 V DC, 11 W, 100% duty cycle, IP65.
Do not assume that another 3/2-way valve is interchangeable simply because the body looks similar. Verify the function, port arrangement, pressure range, temperature range, media compatibility, coil voltage and power, connector arrangement, mounting details and any required approvals against the OEM documentation. Also confirm the part-number supersession through the equipment or valve manufacturer’s records.
2. Check pressure, temperature and media suitability
The stated operating pressure range is 0–10 bar. This is the valve’s specified range; it is not permission to exceed the pressure permitted by the connected actuator, tubing, fittings or machine circuit. Confirm the actual supply pressure with a calibrated gauge or the control-system documentation.
Check the following before applying test pressure:
- There is no trapped pressure on either side of the valve or actuator.
- The working medium is permitted by the OEM or valve documentation. The product data specifies the pressure and temperature limits but does not define a universal media list.
- The surrounding temperature remains between −10 and +60 °C.
- Exhaust air cannot move a linkage, cylinder or other hazardous mechanism unexpectedly.
- Pipework is clean and free from sealant or debris that could obstruct the poppet or exhaust passage.
For a replacement, compare the port markings and pneumatic schematic with the original installation. A 3/2-way valve normally provides three connections and two switching states, but the actual normally open or normally closed arrangement must be confirmed from the valve marking, supplied instructions or the machine schematic rather than assumed.
3. Safety and isolation before testing
Apply the vessel or plant isolation procedure before disconnecting the valve. Isolate and lock out the 24 V DC supply, shut the pneumatic supply, vent trapped pressure and verify zero pressure at the relevant test point. If the valve controls an actuator, secure the actuator against gravity, stored energy or unintended movement.
Safety note: Never remove a pneumatic valve from pressurised pipework. Do not rely only on a closed upstream valve; depressurise and verify. Follow the OEM maintenance manual, site permit system and lock-out/tag-out requirements.
Use suitable eye protection and keep fingers clear of ports and moving actuators. The manual override can operate the valve without electrical power, so treat it as a functional control rather than a harmless test button.

4. Test the 24 V DC solenoid coil
The supplied coil is rated at 24 V DC and 11 W, with 100% duty-cycle capability. At its nominal operating point, the approximate current is:
Current = Power ÷ Voltage = 11 W ÷ 24 V = 0.458 A
This is a nominal value, not a substitute for the manufacturer’s electrical tolerance. Measure the supply at the coil terminals under the actual operating condition, because a voltage drop in a fuse, relay, connector or cable can prevent reliable actuation.
Coil resistance check
- Isolate the 24 V DC supply and prove it is dead.
- Disconnect the coil from the control wiring or connector so parallel circuitry does not affect the measurement.
- Set a multimeter to resistance and measure across the coil terminals.
- Compare the result with the expected nominal resistance calculated from the rating: R = V² ÷ P = 24² ÷ 11 = approximately 52.4 ohms.
- Interpret the reading together with the coil temperature and the manufacturer’s instructions. A significantly high or infinite reading indicates an open circuit; a very low reading may indicate a shorted or damaged winding.
Resistance changes with temperature, meter accuracy and coil construction, so the 52.4-ohm calculation is a reference point, not a universal pass/fail limit. Inspect the coil body, terminals and connector for overheating, corrosion, looseness or water ingress. The IP65 rating applies when the installation and connection are correctly made; it does not make a disconnected or damaged connector suitable for immersion.
Live voltage and actuation check
After completing the resistance check and reconnecting the circuit, restore power only when it is safe to do so. Command the valve and measure the voltage at the coil while it is energised. A healthy control command should provide approximately the rated 24 V DC at the coil, subject to the system’s permitted tolerance. If voltage is absent, investigate the fuse, PLC or relay output, emergency-stop chain, wiring and connector before condemning the valve.
Do not leave a loose coil energised on a removed valve unless the manufacturer’s instructions specifically permit that test. The magnetic field can attract metal objects, and the coil may heat during operation even though it is rated for continuous duty.
5. Test the 3/2-way pneumatic function
Use a regulated, clean test supply and a pressure gauge. Connect the valve according to its marked ports and the supplied IMI Norgren installation and operating instructions. Do not infer the port sequence from a different valve series.
- With the coil de-energised, apply a controlled pressure within 0–10 bar.
- Check the expected spring-return state from the machine schematic or valve instructions. Confirm that the correct service port is connected to the supply or exhaust path for that state.
- Listen and check for leakage at the body, fittings, exhaust and connected actuator. A small amount of leakage caused by a test fitting is not evidence of an internal valve fault, so check connections separately.
- Energise the coil with 24 V DC and observe the change in pneumatic state. The valve should switch positively without excessive delay, chattering or repeated cycling.
- Remove the electrical command. The spring should return the valve to its original state. Confirm that the actuator or downstream device also returns as designed.
- Repeat the test at the intended working pressure, provided it remains within the rated range and the connected equipment is safe to operate.
Record the applied pressure, coil voltage, coil resistance, switching response and leakage observations. If the valve only works when tapped, sticks intermittently or fails to return, isolate it again before inspection. Possible causes include contamination, damaged poppet or seat, incorrect pressure conditions, a weak or damaged spring, coil problems or incorrect pipe connections.
6. Use the manual override correctly
The 2401135 includes a manual override for functional checking or emergency operation where permitted by the equipment procedure. First isolate unexpected movement and confirm that the pneumatic circuit is safe. Operate the override only as described in the supplied instructions; do not use tools or excessive force.
With the coil de-energised, operate the override briefly and observe whether the valve changes state. Release it and confirm that the valve returns as intended. If the override operates the valve but the electrical command does not, focus on the coil, supply and control wiring. If neither the override nor the solenoid produces the expected switching, investigate pressure, porting, contamination and internal mechanical damage.
7. Fault-finding checklist
| Symptom | Likely causes | Checks |
|---|---|---|
| No click or movement | No 24 V DC, open coil, failed control output | Measure voltage at the coil, isolate and measure resistance, check fuse, relay and connector |
| Coil energises but no air change | Incorrect porting, insufficient pressure, stuck poppet, blocked passage | Check schematic, pressure within 0–10 bar, cleanliness and manual override response |
| Valve does not return | Mechanical obstruction, damaged spring, residual pressure or actuator load | Depressurise, inspect safely, verify spring-return state and connected mechanism |
| Intermittent operation | Loose wiring, voltage drop, contamination, overheating or marginal control signal | Monitor coil voltage during operation and inspect terminals, temperature and air quality |
| External leakage | Loose or damaged fitting, seal failure or body damage | Isolate and depressurise, inspect fittings and seals; do not tighten pressurised connections |
8. Replacement and acceptance record
When replacement is necessary, the IMI Herion 2401135 is supplied as new old stock in sealed original packaging with instructions. Verify the part number against the engine or machine parts list before installation. Record the valve identification, coil rating, pressure used for testing, electrical readings and final pneumatic result in the maintenance system.
After installation, perform a controlled leak check and a complete de-energised/energised functional test. Confirm that the spring-return position is the correct safe state for the machine. If the application, port arrangement or media is uncertain, stop and obtain the OEM documentation rather than relying on visual similarity.
FAQ
What is the normal coil resistance of the IMI Herion 2401135?
Using the 24 V, 11 W rating gives approximately 52.4 ohms at the nominal operating point. Treat this as a reference; temperature and manufacturer tolerances affect the measured value.
Can the valve be tested without compressed air?
You can test coil resistance, supply voltage and the manual override mechanically, but pneumatic switching and leakage require a safe, regulated test supply within the 0–10 bar rating.
Does a 3/2-way valve always have the same port arrangement?
No. Confirm the port markings and switching diagram from the valve instructions or machine schematic. Do not assume the normally open or normally closed state.
What should be checked before ordering a replacement?
Verify part number 2401135, 24 V DC coil rating, 3/2-way function, 0–10 bar range, temperature, porting, connector and media suitability against the OEM documentation.